{"data":{"id":"us/46-cfr-111.53-1","jurisdiction":"us","citation":"46 CFR 111.53-1","heading":"-1 General.","body":"(a) Each fuse must—\n(1) Meet the general provisions of Article 240 of NFPA 70 or IEC 60092-202:2016 (both incorporated by reference; see “§ 110.10-1 of this subchapter) as appropriate.\n(2) Have an interrupting rating sufficient to interrupt the asymmetrical RMS short-circuit current at the point of application; and\n(b) Renewable link cartridge-type fuses must not be used.\n(c) Each fuse installation must provide for ready access to test the condition of the fuse.","path":["Title 46—Shipping","CHAPTER I—COAST GUARD, DEPARTMENT OF HOMELAND SECURITY","SUBCHAPTER J—ELECTRICAL ENGINEERING","PART 111—ELECTRIC SYSTEMS—GENERAL REQUIREMENTS","Subpart 111.53—Fuses"],"source_url":"https://www.ecfr.gov/api/versioner/v1/full/2026-08-25/title-46.xml","current_through":"2026-08-25","vintage":"","retrieved_at":"2026-08-27T02:26:22Z","sha256":"0861a579b4acecef951f372bc3dffb091c4c1e87e6c3851a6dc614d341109c09","source_id":"us-cfr","stale":true,"prev":"us/46-cfr-111.51-5","next":"us/46-cfr-111.54-1"},"notice":"GroundRules: Original legal text. Not legal advice."}