{"data":{"id":"us/46-cfr-111.60-2","jurisdiction":"us","citation":"46 CFR 111.60-2","heading":"-2 Specialty cable for communication and RF applications.","body":"Specialty cable such as certain coaxial cable that cannot pass the flammability test contained in IEEE 1580, test FV-2/VW-1 of ANSI/UL 2556, IEC 60332-3-21:2018, or IEC 60332-3-22:2018 (all incorporated by reference; see § 110.10-1 of this subchapter) because of unique properties of construction, must:\n(a) Be installed physically separate from all other cable; and\n(b) Have fire stops installed—\n(1) At least every 7 meters (21.5 feet) vertically, up to a maximum of 2 deck heights;\n(2) At least every 15 meters (46 feet) horizontally;\n(3) At each penetration of an A or B Class boundary;\n(4) At each location where the cable enters equipment; or\n(5) In a cableway that has an A-60 fire rating.","path":["Title 46—Shipping","CHAPTER I—COAST GUARD, DEPARTMENT OF HOMELAND SECURITY","SUBCHAPTER J—ELECTRICAL ENGINEERING","PART 111—ELECTRIC SYSTEMS—GENERAL REQUIREMENTS","Subpart 111.60—Wiring Materials and Methods"],"source_url":"https://www.ecfr.gov/api/versioner/v1/full/2026-08-25/title-46.xml","current_through":"2026-08-25","vintage":"","retrieved_at":"2026-08-27T02:26:22Z","sha256":"42576e6aab02c4185ec06c432c6e45cc1ae84ea62dd2a09b3f950fdd8c7a4f64","source_id":"us-cfr","stale":true,"prev":"us/46-cfr-111.60-1","next":"us/46-cfr-111.60-3"},"notice":"GroundRules: Original legal text. Not legal advice."}