{"data":{"id":"us/46-cfr-111.79-15","jurisdiction":"us","citation":"46 CFR 111.79-15","heading":"-15 Receptacles for refrigerated containers.","body":"Receptacles for refrigerated containers must meet one of the following:\n(a) Each receptacle for refrigerated containers must have a switch interlocked in such a way that the receptacle's contacts are deenergized before the making or breaking of the connection between the plug and receptacle contacts.\n(b) Each group of receptacles for refrigerated containers must have:\n(1) A switch near the receptacles that disconnects all power to those receptacles; and\n(2) A sign stating that the switch should be opened before cables are disconnected from the receptacles or refrigerated containers.\n(c) Each receptacle for refrigerated containers must be designed for circuit breaking service.","path":["Title 46—Shipping","CHAPTER I—COAST GUARD, DEPARTMENT OF HOMELAND SECURITY","SUBCHAPTER J—ELECTRICAL ENGINEERING","PART 111—ELECTRIC SYSTEMS—GENERAL REQUIREMENTS","Subpart 111.79—Receptacles"],"source_url":"https://www.ecfr.gov/api/versioner/v1/full/2026-08-25/title-46.xml","current_through":"2026-08-25","vintage":"","retrieved_at":"2026-08-27T02:26:22Z","sha256":"4ebd341a82c7d080e4cdc9a20cda2be099a0c587739dfe062849779b4725e997","source_id":"us-cfr","stale":true,"prev":"us/46-cfr-111.79-13","next":"us/46-cfr-111.81-1"},"notice":"GroundRules: Original legal text. Not legal advice."}