{"data":{"id":"us/46-cfr-112.30-5","jurisdiction":"us","citation":"46 CFR 112.30-5","heading":"-5 Transfer of emergency loads.","body":"If there is a reduction of potential of the normal source by 15 to 40 percent, the emergency loads under § 112.15-5 must transfer automatically from the normal source to the emergency power source.","path":["Title 46—Shipping","CHAPTER I—COAST GUARD, DEPARTMENT OF HOMELAND SECURITY","SUBCHAPTER J—ELECTRICAL ENGINEERING","PART 112—EMERGENCY LIGHTING AND POWER SYSTEMS","Subpart 112.30—Emergency Systems Having an Automatically Connected Storage Battery as the Sole Emergency Power Source"],"source_url":"https://www.ecfr.gov/api/versioner/v1/full/2026-08-25/title-46.xml","current_through":"2026-08-25","vintage":"","retrieved_at":"2026-08-27T02:26:22Z","sha256":"723ec5775eb8ef84c9796080c2543441097b1064a87691c28c2e115f1642f5d8","source_id":"us-cfr","stale":true,"prev":"us/46-cfr-112.30-3","next":"us/46-cfr-112.30-10"},"notice":"GroundRules: Original legal text. Not legal advice."}