{"data":{"id":"us/46-cfr-132.330","jurisdiction":"us","citation":"46 CFR 132.330","heading":"Fire monitors.","body":"(a) Each fire monitor of the fire main system must be fitted with a shut-off valve at the monitor and at the connection to the fire main discharge manifold required by § 132.120(h) of this part.\n(b) Fire monitor piping must comply with § 132.110 of this part.\n(c) Each fire monitor must be protected against over-pressure.","path":["Title 46—Shipping","CHAPTER I—COAST GUARD, DEPARTMENT OF HOMELAND SECURITY","SUBCHAPTER L—OFFSHORE SUPPLY VESSELS","PART 132—FIRE-PROTECTION EQUIPMENT","Subpart C—Miscellaneous"],"source_url":"https://www.ecfr.gov/api/versioner/v1/full/2026-08-25/title-46.xml","current_through":"2026-08-25","vintage":"","retrieved_at":"2026-08-27T02:26:22Z","sha256":"ff511f9c23585a1c3b1949b8afc94f8c358e9a66d2a102698ceb98dc8d1347e5","source_id":"us-cfr","stale":true,"prev":"us/46-cfr-132.320","next":"us/46-cfr-132.340"},"notice":"GroundRules: Original legal text. Not legal advice."}