{"data":{"id":"us/46-cfr-154.1160","jurisdiction":"us","citation":"46 CFR 154.1160","heading":"Monitor coverage of system.","body":"The coverage of each dry chemical system monitor under § 154.1150 must not exceed:\n(a) 10 m (32.8 ft.) at 10 kg/sec (22 lb/sec);\n(b) 30 m (98.4 ft.) at 25 kg/sec (55 lb/sec);\n(c) 40 m (131.2 ft.) at 45 kg/sec (99 lb/sec);\n(d) An interpolation between 10 m (32.8 ft.) at 10 kg/sec (22 lb/sec) and 30 m (98.4 ft.) at 25 kg/sec (55 lb/sec); or\n(e) An interpolation between 30 m (98.4 ft.) at 25 kg/sec (55 lb/sec) and 40 m (131.2 ft.) at 45 kg/sec (99 lb/sec).","path":["Title 46—Shipping","CHAPTER I—COAST GUARD, DEPARTMENT OF HOMELAND SECURITY","SUBCHAPTER O—CERTAIN BULK DANGEROUS CARGOES","PART 154—SAFETY STANDARDS FOR SELF-PROPELLED VESSELS CARRYING BULK LIQUEFIED GASES","Subpart C—Design, Construction and Equipment"],"source_url":"https://www.ecfr.gov/api/versioner/v1/full/2026-08-25/title-46.xml","current_through":"2026-08-25","vintage":"","retrieved_at":"2026-08-27T02:26:22Z","sha256":"bf334812f446a38a8af8045dd4731894562d5cd9b8696eeeffad3f545559daa6","source_id":"us-cfr","stale":true,"prev":"us/46-cfr-154.1155","next":"us/46-cfr-154.1165"},"notice":"GroundRules: Original legal text. Not legal advice."}