{"data":{"id":"us/46-cfr-28.855","jurisdiction":"us","citation":"46 CFR 28.855","heading":"Electrical distribution systems.","body":"(a) Each electrical distribution system which has a neutral bus or conductor must have the neutral bus or conductor grounded.\n(b) A grounded electrical distribution system must have only one connection to ground. This ground connection must be at the switchboard.","path":["Title 46—Shipping","CHAPTER I—COAST GUARD, DEPARTMENT OF HOMELAND SECURITY","SUBCHAPTER C—UNINSPECTED VESSELS","PART 28—REQUIREMENTS FOR COMMERCIAL FISHING INDUSTRY VESSELS","Subpart G—Aleutian Trade Act Vessels"],"source_url":"https://www.ecfr.gov/api/versioner/v1/full/2026-08-25/title-46.xml","current_through":"2026-08-25","vintage":"","retrieved_at":"2026-08-27T02:26:22Z","sha256":"7f327df34f19ee9f0f6eb9b779678630d3d882cc5eaecfbfd453a5dd19832c06","source_id":"us-cfr","stale":true,"prev":"us/46-cfr-28.850","next":"us/46-cfr-28.860"},"notice":"GroundRules: Original legal text. Not legal advice."}