{"data":{"id":"us/46-cfr-76.33-10","jurisdiction":"us","citation":"46 CFR 76.33-10","heading":"-10 Location and spacing of accumulators.","body":"(a) Smoke accumulators must be located overhead in each compartment. Where liable to physical damage, the accumulators and piping must be suitably protected.\n(b) No spot on the overhead of a protected space may be more than 40 feet from an accumulator.\n(c) Accumulators must not be located closer to the opening of a ventilator than three times the diameter or equivalent diameter of the opening.","path":["Title 46—Shipping","CHAPTER I—COAST GUARD, DEPARTMENT OF HOMELAND SECURITY","SUBCHAPTER H—PASSENGER VESSELS","PART 76—FIRE PROTECTION EQUIPMENT","Subpart 76.33—Smoke Detection System, Details"],"source_url":"https://www.ecfr.gov/api/versioner/v1/full/2026-08-25/title-46.xml","current_through":"2026-08-25","vintage":"","retrieved_at":"2026-08-27T02:26:22Z","sha256":"40abcd6a8db59467ab6ea6512dae7e34f0b0aa0ff61407b7601e08514d9de722","source_id":"us-cfr","stale":true,"prev":"us/46-cfr-76.33-5","next":"us/46-cfr-76.33-15"},"notice":"GroundRules: Original legal text. Not legal advice."}