{"data":{"id":"us/49-cfr-192.359","jurisdiction":"us","citation":"49 CFR 192.359","heading":"Customer meter installations: Operating pressure.","body":"(a) A meter may not be used at a pressure that is more than 67 percent of the manufacturer's shell test pressure.\n(b) Each newly installed meter manufactured after November 12, 1970, must have been tested to a minimum of 10 p.s.i. (69 kPa) gage.\n(c) A rebuilt or repaired tinned steel case meter may not be used at a pressure that is more than 50 percent of the pressure used to test the meter after rebuilding or repairing.","path":["Title 49—Transportation","Subtitle B—Other Regulations Relating to Transportation","CHAPTER I—PIPELINE AND HAZARDOUS MATERIALS SAFETY ADMINISTRATION, DEPARTMENT OF TRANSPORTATION","SUBCHAPTER D—PIPELINE SAFETY","PART 192—TRANSPORTATION OF NATURAL AND OTHER GAS BY PIPELINE: MINIMUM FEDERAL SAFETY STANDARDS","Subpart H—Customer Meters, Service Regulators, and Service Lines"],"source_url":"https://www.ecfr.gov/api/versioner/v1/full/2026-08-25/title-49.xml","current_through":"2026-08-25","vintage":"","retrieved_at":"2026-08-27T02:26:34Z","sha256":"f750adab0fc7352d8118c0ef46b703528eab84d35e22d153409c0e3cec66e11e","source_id":"us-cfr","stale":true,"prev":"us/49-cfr-192.357","next":"us/49-cfr-192.361"},"notice":"GroundRules: Original legal text. Not legal advice."}