{"data":{"id":"us/49-cfr-192.365","jurisdiction":"us","citation":"49 CFR 192.365","heading":"Service lines: Location of valves.","body":"(a) Relation to regulator or meter. Each service-line valve must be installed upstream of the regulator or, if there is no regulator, upstream of the meter.\n(b) Outside valves. Each service line must have a shut-off valve in a readily accessible location that, if feasible, is outside of the building.\n(c) Underground valves. Each underground service-line valve must be located in a covered durable curb box or standpipe that allows ready operation of the valve and is supported independently of the service lines.","path":["Title 49—Transportation","Subtitle B—Other Regulations Relating to Transportation","CHAPTER I—PIPELINE AND HAZARDOUS MATERIALS SAFETY ADMINISTRATION, DEPARTMENT OF TRANSPORTATION","SUBCHAPTER D—PIPELINE SAFETY","PART 192—TRANSPORTATION OF NATURAL AND OTHER GAS BY PIPELINE: MINIMUM FEDERAL SAFETY STANDARDS","Subpart H—Customer Meters, Service Regulators, and Service Lines"],"source_url":"https://www.ecfr.gov/api/versioner/v1/full/2026-08-25/title-49.xml","current_through":"2026-08-25","vintage":"","retrieved_at":"2026-08-27T02:26:34Z","sha256":"31ffee5ad7c2a2c038008ce570920a861ae03aa1061f17fc5d087f1d38fa8218","source_id":"us-cfr","stale":true,"prev":"us/49-cfr-192.363","next":"us/49-cfr-192.367"},"notice":"GroundRules: Original legal text. Not legal advice."}