IC 8-1-42-13: Underground cables; aboveground infrastructure; depth of buried cables; cables and lines outside of project site

Read at publisher ↗
Where this section sits in the code
  1. TITLE 8. UTILITIES AND TRANSPORTATION
  2. ARTICLE 1. UTILITIES GENERALLY
  3. Chapter 42. Default Standards for Commercial Solar Energy Systems

Sec. 13. Except as otherwise allowed by IC 36-7-4-1109, if a project owner installs a CSE system in a unit, all cables of up to thirty-four and one-half (34.5) kilovolts that are located between inverter locations and project substations shall be located and maintained underground, as feasible. Other solar infrastructure, such as module-to-module collection cables, transmission lines, substations, junction boxes, and other typical aboveground infrastructure may be located and maintained above ground. Buried cables shall be at a depth of at least thirty-six (36) inches below grade or, if necessitated by onsite conditions, at a greater depth. Cables and lines located outside of the CSE system project site may:

(1) be located above ground; or

(2) in the case of cables or lines of up to thirty-four and one-half (34.5) kilovolts, be buried underground at:

(A) a depth of at least forty-eight (48) inches below grade, so as to not interfere with drainage tile or ditch repairs; or

(B) another depth, as necessitated by conditions;

as determined in consultation with the landowner.