Section 210.11 (C)(4) – Add a new Informational Note to Section 210.11(C)(4) to read as follows:
Informational Note: See Residential Provision of the New York City Energy Conservation Code, for additional Electrical Vehicle (EV) requirements.
Section 210.11(C)(5) – Add a new Section 210.11(C)(5) to read as follows:
(5) Air-Conditioning Branch Circuit. In addition to the number of branch circuits required by other parts of this section, an individual branch circuit shall be provided for each air-conditioning receptacle outlet required by 210.52(J).