N.Y.C. Admin. Code § 27-513: § 27-513 Exits.

Read at publisher ↗
Where this section sits in the code
  1. New York City Administrative Code
  2. Title 27
  3. Chapter 1: Building Code

Notwithstanding any other requirements of subchapters six and eight of this chapter, travel distance to an exit from any point within a tent or air-supported structure shall not exceed seventy-five feet. Exit doors in air-supported structures shall close automatically against normal operational pressures. Opening force at the edge of such doors shall not exceed fifteen pounds, with the structure at operational pressure. Exit doors shall be located in frames so constructed that they will remain operative and support the weight of the structure in a state of total collapse.