N.Y.C. Admin. Code § 27-863.01: § 27-863.01 Chimney limitations and tests.
Where this section sits in the code
- New York City Administrative Code
- Title 27
- Chapter 1: Building Code
No solid fuel fireplace, fireplace stove or room heater shall be installed or altered unless connected to a chimney which complies with the limitations and testing requirements set forth in table 15-6.1.
TABLE 15-6.1 Chimney Limitations and Tests for Solid Fuel Fireplaces, Fireplace Stoves and Room Heaters
Occupancy
Reference Standard
Test Standard
Temperature
Number of Tests
J-2 & J-3 limited to 40 feet and three stories
RS 15-15
UL 127, as Modified
1700°F
1 test
J-2 & J-3 limited
RS 15-9
UL 103HT
2100°F – 10 min.
3 tests
to 75 feet
RS 15-12
ULC 629M
2100°F – 30 min.
3 tests
All other occupancies and all buildings greater than 75 feet in height
RS 15-10
UL 959
2000°F to Equilibrium and 2300°F – 30 min.
1 test
3 tests
Table 15-6 of Subdivision (c) of Section 27-863 and Section 27-861
No Standard
Unlisted High Temp. Chimney with Required Thickness Listed in Table 15-6
No test
Note: Chimneys accepted pursuant to reference standard RS 15-10 or Table 15-6 may be used in lieu of chimneys accepted pursuant to reference standards RS 15-9, RS 15-12 and RS 15-15.Chimneys accepted pursuant to reference standards RS 15-9 or RS 15-12 may be used in lieu of chimneys accepted pursuant to reference standard RS 15-15.