N.Y.C. Admin. Code § 700.3: Section 700.3
Where this section sits in the code
- New York City Administrative Code
- Title 28
- Chapter 11: The New York City Electrical Code
Section 700.3 – Revise Section 700.3(A) to read as follows:
(A) Conduct or Witness Test. Inspection and testing requirements shall be performed in accordance with Chapter 17 of the New York City Building Code.
Section 700.3 – Revise Section 700.3(B) to read as follows:
(B) Tested Periodically. Systems shall be periodically tested in accordance with the schedule and requirements set forth in the New York City Fire Code to ensure the systems are maintained in proper operating condition.
Section 700.3 – Revise Section 700.3(D) to read as follows:
(D) Written Record. A written record shall be kept on premises of such tests and maintenance.
Section 700.3 – Revise Section 700.3(E) to read as follows:
(E) Testing Under Load. Means for testing all emergency lighting and power systems during maximum anticipated load conditions shall be provided.
Informational Note: For information on testing and maintenance of emergency power supply systems (EPSSs), see the New York City Fire Code and its amended referenced standard NFPA 110, Standard for Emergency and Standby Power Systems.
Section 700.3 – Revise the opening paragraph in Section 700.3(F) to read as follows:
(F) Temporary Source of Power for Maintenance or Repair of the Alternate Source of Power. If the emergency system relies on a single alternate source of power, the emergency system shall include permanent switching means to connect a portable or temporary alternate source of power, which shall be available for the duration of the maintenance or repair. The permanent switching means to connect a portable or temporary alternate source of power shall comply with the following: