N.Y.C. Admin. Code § 705.30: Section 705.30
Where this section sits in the code
- New York City Administrative Code
- Title 28
- Chapter 11: The New York City Electrical Code
Section 705.30 – Revise Section 705.30(C) to read as follow:
(C) Transformers. The following apply to the installation of transformers:
(1) For the purpose of overcurrent protection, the primary side of transformers with sources on each side shall be the side connected to the largest source of available fault current.
(2) Transformer secondary conductors shall be protected in accordance with 240.21(C).