N.Y.C. Admin. Code § 760.136: Section 760.136
Where this section sits in the code
- New York City Administrative Code
- Title 28
- Chapter 11: The New York City Electrical Code
Section 760.136 – Revise Section 760.136(D)(2) to read as follows:
(2) The circuit conductors operate at 150 volts or less to ground and also comply with 1 of the following:
a. The fire alarm power-limited circuits are installed using Type FPLP “NYC Certified Fire Alarm Cable” provided these power-limited cable conductors extending beyond the jacket are separated by a minimum of 0.25 in. (6 mm) or by a nonconductive sleeve or nonconductive barrier from all other conductors.
b. DELETED.
Section 760.136 – Revise Section 760.136(F) to read as follows:
(F) In Hoistways. In hoistways, power-limited fire alarm circuit conductors shall be installed in rigid metal conduit, intermediate metal conduit, or electrical metallic tubing. For elevators or similar equipment, these conductors shall be permitted to be installed as provided in 620.21.
Section 760.136 – Revise Section 760.136(G)(1) to read as follows:
(1) Either (a) all of the electric light, power, Class 1, nonpower-limited fire alarm, and medium-power network powered broadband communications circuit conductors or (b) all of the power-limited fire alarm circuit conductors are in a raceway or metal-sheathed or metal-clad cables.