N.Y.C. Admin. Code § BC 1908: Section BC 1908: Modifications to ACI 318
Where this section sits in the code
- New York City Administrative Code
- Title 28
- Chapter 7: New York City Building Code
1908.1 General.
The text of ACI 318 shall be modified as indicated in Sections 1908.1.1 through 1908.1.10.
1908.1.1 ACI 318, Section 2.3.
Modify existing definitions and add the following definitions to ACI 318, Section 2.3.
DESIGN DISPLACEMENT. Total lateral displacement expected for the design-basis earthquake, as specified by Section 12.8.6 of ASCE 7.
DETAILED PLAIN CONCRETE STRUCTURAL WALL. A wall complying with the requirements of Chapter 14 including 14.6.2.
ORDINARY PRECAST STRUCTURAL WALL. A precast wall complying with the requirements of ACI 318 except for Chapters 14, 17 and 18.
ORDINARY REINFORCED CONCRETE STRUCTURAL WALL. A cast-in-place wall complying with the requirements of ACI 318 except for Chapters 14, 17 and 18.
ORDINARY STRUCTURAL PLAIN CONCRETE WALL. A wall complying with the requirements of Chapter 14, excluding 14.6.2.
SPECIAL STRUCTURAL WALL. A cast-in-place or precast wall complying with the requirements of 18.2.4 through 18.2.8, 18.10 and 18.11, as applicable, in addition to the requirements for ordinary reinforced concrete structural walls or ordinary precast structural walls, as applicable. Where ASCE 7 refers to a "special reinforced concrete structural shear wall", it shall be deemed to mean a "special structural wall".
1908.1.2 ACI 318, Section 8.7.2.
Modify ACI 318, Section 8.7.2.3 and 8.7.2.4, and add new sections 8.7.2.5 and 8.7.2.6 to read as follows:
8.7.2.3 – For prestressed slabs with Banded-Distributed tendon placement, the maximum spacing s of tendons or groups of tendons in the distributed direction shall be the lesser of 8h and 5ft.
8.7.2.4 – The placement of tendons banded in both directions over the supports in two-way slabs is allowed. For Banded-Banded tendon placement, all provisions of ACI-318 Chapter 8 shall apply, except section 8.7.2.3, referring to the maximum tendon spacing limitation.
8.7.2.5 – At locations where the average effective prestress is not distributed, the two-way slab shall be designed using non-prestressed reinforcement.
8.7.2.6 – Concentrated Loads and openings shall be considered in determining tendon spacing.
1908.1.3 ACI 318, Section 14.1.4.
Delete ACI 318, Section 14.1.4 and replace with the following:
14.1.4 – Plain concrete in structures assigned to Seismic Design Category C or D.
14.1.4.1 – Structures assigned to Seismic Design Category C or D shall not have elements of structural plain concrete, except as follows:
(a) Structural plain concrete basement, foundation or other walls below the base, as defined in ASCE 7, are permitted in detached one- and two-family dwellings three stories or less in height constructed with stud-bearing walls. In dwellings assigned to Seismic Design Category D, the height of the wall shall not exceed 8 feet (2438 mm), the thickness shall be not less than 7 1/2 inches (190 mm), and the wall shall retain no more than 4 feet (1219 mm) of unbalanced fill. Walls shall have reinforcement in accordance with 14.6.1.
(b) Isolated footings of plain concrete supporting pedestals or columns are permitted, provided the projection of the footing beyond the face of the supported member does not exceed the footing thickness.
Exception: In detached one- and two-family dwellings three stories or less in height, the projection of the footing beyond the face of the supported member is permitted to exceed the footing thickness.
(c) Plain concrete footings supporting walls are permitted, provided the footings have at least two continuous longitudinal reinforcing bars. Bars shall not be smaller than No. 4 and shall have a total area of not less than 0.002 times the gross cross-sectional area of the footing. For footings that exceed 8 inches (203 mm) in thickness, a minimum of one bar shall be provided at the top and bottom of the footing. Continuity of reinforcement shall be provided at corners and intersections.
Exceptions:
1. In Seismic Design Categories A, B and C, detached one- and two-family dwellings three stories or less in height constructed with stud-bearing walls are permitted to have plain concrete footings without longitudinal reinforcement.
2. For foundation systems consisting of a plain concrete footing and a plain concrete stemwall, a minimum of one bar shall be provided at the top of the stem wall and at the bottom of the footing.
3. Where a slab on ground is cast monolithically with the footing, one No. 5 bar is permitted to be located at either the top of the slab or bottom of the footing.
1908.1.4 ACI 318, Section 14.6.
Modify ACI 318, Section 14.6 by adding new Section 14.6.2 to read as follows:
14.6.2 – Detailed plain concrete structural walls.
14.6.2.1 – Detailed plain concrete structural walls are walls conforming to the requirements of ordinary structural plain concrete walls and 14.6.2.2.
14.6.2.2 – Reinforcement shall be provided as follows:
(a) Vertical reinforcement of at least 0.20 square inch (129 mm
2
) in cross-sectional area shall be provided continuously from support to support at each corner, at each side of each opening and at the ends of walls. The continuous vertical bar required beside an opening is permitted to substitute for one of the two No. 5 bars required by 14.6.1.
(b) Horizontal reinforcement at least 0.20 square inch (129 mm
2
) in cross-sectional area shall be provided:
1. Continuously at structurally connected roof and floor levels and at the top of walls;
2. At the bottom of load-bearing walls or in the top of foundations where doweled to the wall; and
3. At a maximum spacing of 120 inches (3048 mm).
Reinforcement at the top and bottom of openings, where used in determining the maximum spacing specified in Item 3 above, shall be continuous in the wall.
1908.1.5 ACI 318, Section 15.3.
Modify ACI 318 by adding Section 15.3.2 to read as follows:
15.3.2 – When the specified compressive strength of concrete in a column is greater than 1.4 times that specified for a floor system, the following additional requirements shall be adhered to:
1. All of the design provisions of Section 15.3 (unmodified) are adhered to.
2. The concrete construction is supervised and inspected continuously by a full-time professional engineer responsible for the concrete placement special inspection. Such professional engineer shall not delegate this responsibility to any subordinates.
1908.1.6 ACI 318, Section 17.2.3.
Modify ACI 318 Sections 17.2.3.4.2, 17.2.3.4.3(d) and 17.2.3.5.2 to read as follows:
17.2.3.4.2 – Where the tensile component of the strength-level earthquake force applied to anchors exceeds 20 percent of the total factored anchor tensile force associated with the same load combination, anchors and their attachments shall be designed in accordance with 17.2.3.4.3. The anchor design tensile strength shall be determined in accordance with 17.2.3.4.4.
Exception: Anchors designed to resist wall out-of-plane forces with design strengths equal to or greater than the force determined in accordance with ASCE 7 Equation 12.11-1 or 12.14-10 shall be deemed to satisfy Section 17.2.3.4.3(d).
17.2.3.4.3(d) – The anchor or group of anchors shall be designed for the maximum tension obtained from design load combinations that include E, with E increased by W
0
. The anchor design tensile strength shall be calculated from 17.2.3.4.4.
17.2.3.5.2 – Where the shear component of the strength-level earthquake force applied to anchors exceeds 20 percent of the total factored anchor shear force associated with the same load combination, anchors and their attachments shall be designed in accordance with 17.2.3.5.3. The anchor design shear strength for resisting earthquake forces shall be determined in accordance with 17.5.
Exceptions:
1. For the calculation of the in-plane shear strength of anchor bolts attaching wood sill plates of bearing or nonbearing walls of light-frame wood structures to foundations or foundation stem walls, the in-plane shear strength in accordance with 17.5.2 and 17.5.3 need not be computed and 17.2.3.5.3 shall be deemed to be satisfied provided all of the following are met:
1.1. The allowable in-plane shear strength of the anchor is determined in accordance with AWC NDS Table 12E for lateral design values parallel to grain.
1.2. The maximum anchor nominal diameter is 5/8 inch (16 mm).
1.3. Anchor bolts are embedded into concrete a minimum of 7 inches (178 mm).
1.4. Anchor bolts are located a minimum of 1 3/4 inches (45 mm) from the edge of the concrete parallel to the length of the wood sill plate.
1.5. Anchor bolts are located a minimum of 15 anchor diameters from the edge of the concrete perpendicular to the length of the wood sill plate.
1.6. The sill plate is 2-inch (51 mm) or 3-inch (76 mm) nominal thickness.
2. For the calculation of the in-plane shear strength of anchor bolts attaching cold-formed steel track of bearing or nonbearing walls of light-frame construction to foundations or foundation stem walls, the in-plane shear strength in accordance with 17.5.2 and 17.5.3 need not be computed and 17.2.3.5.3 shall be deemed to be satisfied provided all of the following are met:
2.1. The maximum anchor nominal diameter is 5/8 inch (16 mm).
2.2. Anchors are embedded into concrete a minimum of 7 inches (178 mm).
2.3. Anchors are located a minimum of 1 3/4 inches (45 mm) from the edge of the concrete parallel to the length of the track.
2.4. Anchors are located a minimum of 15 anchor diameters from the edge of the concrete perpendicular to the length of the track.
2.5. The track is 33 to 68 mil (0.84 mm to 1.73 mm) designation thickness.
Allowable in-plane shear strength of exempt anchors, parallel to the edge of concrete, shall be permitted to be determined in accordance with AISI S100, Section J3.3.1.
3. In light-frame construction bearing or non-bearing walls, shear strength of concrete anchors less than or equal to 1 inch (25 mm) in diameter attaching sill plate or track to foundation or foundation stem wall need not satisfy 17.2.3.5.3(a) through (c) when the design strength of the anchors is determined in accordance with 17.5.2.1(c).
1908.1.7 ACI 318, Section 18.2.1.
Modify ACI 318 Sections 18.2.1.2 and 18.2.1.6 to read as follows:
18.2.1.2 – Structures assigned to Seismic Design Category A shall satisfy requirements of Chapters 1 through 17 and 19 through 26; Chapter 18 does not apply. Structures assigned to Seismic Design Category B, C, or D also shall satisfy 18.2.1.3 through 18.2.1.7, as applicable. Except for structural elements of plain concrete complying with Section 1908.1.2 of the New York City Building Code, structural elements of plain concrete are prohibited in structures assigned to Seismic Design Category C or D.
18.2.1.6 – Structural systems designated as part of the seismic force-resisting system shall be restricted to those permitted by ASCE 7 as modified by Chapter 16 of the New York City Building Code. Except for Seismic Design Category A, for which Chapter U8 does not apply, the following provisions shall be satisfied for each structural system designated as part of the seismic force-resisting system, regardless of the Seismic Design Category:
(a) Ordinary moment frames shall satisfy 18.3.
(b) Ordinary reinforced concrete structural walls and ordinary precast structural walls need not satisfy any provisions in Chapter 18.
(c) Intermediate moment frames shall satisfy 18.4.
(d) Intermediate precast structural walls shall satisfy 18.5.
(e) Special moment frames shall satisfy 18.6 through 18.9.
(f) Special structural walls shall satisfy 18.10.
(g) Special structural walls constructed using precast concrete shall satisfy 18.11.
All special moment frames and special structural walls shall also satisfy 18.2.4 through 18.2.8.
1908.1.8 ACI 318, Section 18.5.
Modify ACI 318, Section 18.5, by adding new Section 18.5.2.2 and renumbering existing Sections 18.5.2.2 and 18.5.2.3 to become 18.5.2.3 and 18.5.2.4, respectively.
18.5.2.2 – Connections that are designed to yield shall be capable of maintaining 80 percent of their design strength at the deformation induced by the design displacement or shall use Type 2 mechanical splices.
18.5.2.3 – Elements of the connection that are not designed to yield shall develop at least 1.5 S
y
.
18.5.2.4 – In structures assigned to Seismic Design Category D, wall piers shall be designed in accordance with Section 18.10.8 or 18.14 in ACI 318.
1908.1.9 ACI 318, Section 18.11.
Modify ACI 318, Section 18.11.2 to read as follows:
18.11.2.1 – Special structural walls constructed using precast concrete shall satisfy all the requirements of Section 18.10 for cast-in-place special structural walls in addition to Section 18.5.2.
1908.1.10 ACI 318, Section 18.13.1.1.
Modify ACI 318, Section 18.13.1.1, to read as follows:
18.13.1.1 – Foundations resisting earthquake-induced forces or transferring earthquake-induced forces between a structure and ground shall comply with the requirements of Section 18.13 and other applicable provisions of ACI 318 unless modified by Chapter 18 of the New York City Building Code.
1908.1.11 ACI 318, Section 24.2.3.5.
Add the following to Section 24.2.3.5:
When calculating M
a
, consideration shall be given to loads imposed during construction.