N.Y.C. Admin. Code § BC 422: Section BC 422: Ambulatory Care Facilities
Where this section sits in the code
- New York City Administrative Code
- Title 28
- Chapter 7: New York City Building Code
422.1 General.
Ambulatory care facilities shall comply with the provisions of Sections 422.1 through 422.5 and other applicable provisions of this code.
422.2 Separation.
Ambulatory care facilities, where there is the potential for four or more care recipients who will be incapable of self-preservation at any time, whether rendered incapable by staff or staff accepted responsibility for a care recipient already incapable, shall be separated from adjacent spaces, corridors or tenants with a fire partition installed in accordance with Section 708.
422.3 Smoke compartments.
Where the aggregate area of one or more ambulatory care facilities is greater than 10,000 square feet (929 m
2
) on one story, the story shall be provided with a smoke barrier to subdivide the story into no fewer than two smoke compartments. The area of any one such smoke compartment shall be not greater than 22,500 square feet (2092 m
2
). The distance of travel from any point in a smoke compartment to a smoke barrier door shall be not greater than 200 feet (60 960 mm). The smoke barrier shall be installed in accordance with Section 709 with the exception that smoke barriers shall be continuous from outside wall to an outside wall, a floor to a floor, or from a smoke barrier to a smoke barrier or a combination thereof.
422.3.1 Means of egress.
Where ambulatory care facilities require smoke compartmentation in accordance with Section 422.3 of this code, the fire protection and emergency preparedness plans shall comply with the applicable provisions of the New York City Fire Code and shall be in accordance with Section 1001.4 of this code.
422.3.2 Refuge area.
Not less than 30 net square feet (2.8 m
2
) for each nonambulatory care recipient shall be provided within the aggregate area of corridors, care recipient rooms, treatment rooms, lounge or dining areas and other low-hazard areas within each smoke compartment. Each occupant of an ambulatory care facility shall be provided with access to a refuge area without passing through or utilizing adjacent tenant spaces.
422.3.3 Independent egress.
A means of egress shall be provided from each smoke compartment created by smoke barriers without having to return through the smoke compartment from which means of egress originated.
422.4 Automatic sprinkler systems.
Automatic sprinkler systems shall be provided for ambulatory care facilities in accordance with Section 903.2.2.
422.5 Fire alarm systems.
A fire alarm system shall be provided for ambulatory care facilities in accordance with Section 907.2.2.