N.Y.C. Admin. Code § EBC D504: D504 Fireproof stair enclosures (MDL 148(3)).
Where this section sits in the code
- New York City Administrative Code
- Title 28
- Chapter 12: The New York City Existing Building Code (effective July 17, 2027)
Every stair, fire-stair, and fire-tower shall be completely separated from every other stair, fire-stair, and fire-tower and from every public hall and shaft by fireproof walls, with fireproof doors and assemblies, with the doors self-closing and without transoms, at all openings. The doors giving access to such stairs shall not be held open by any device whatsoever.
Exceptions:
1. In dwellings 2 stories or less in height such walls shall be permitted to be constructed as 1-hour fire barriers in lieu of being fireproof.
2. In lieu of fireproof walls, such noncombustible walls shall be permitted to have a 2-hour fire-resistive rating where a full system of automatic sprinklers is installed throughout the building with a water-flow alarm connected to a central supervising station, and hard-wired smoke and carbon monoxide alarms or detectors are installed throughout the building as required for new construction in accordance with
Chapter 9
of the
New York City Building Code
.
Collected 2026-09-06T02:48:57Z. Source file · JSON