N.Y.C. Admin. Code § FC 2305: Section FC 2305: Operation and Maintenance of Liquid Motor Fuel-Dispensing Facilities
Where this section sits in the code
- New York City Administrative Code
- Title 29
- Chapter 2: New York City Fire Code
2305.1 Tank filling operations for liquid motor fuel.
Delivery operations to tanks for liquid motor fuel shall comply with the requirements of FC 2305.1.1 through 2305.1.3 and the applicable requirements of FC Chapter 57.
2305.1.1 Delivery vehicle location.
Where liquid delivery to a motor fuel storage tank is accomplished by positive-pressure operation, cargo tanks making delivery shall be positioned a minimum of 25 feet (7620 mm) from tanks receiving flammable liquids and 15 feet (4572 mm) from tanks receiving combustible liquids. During delivery, a cargo tank shall not obstruct a public street, private road, block motorists' view of roadways or impede the movement of vehicles or pedestrians.
2305.1.2 Tank capacity calculation.
The driver, operator or attendant of a cargo tank shall, before making delivery to a tank, determine the unfilled, available capacity of such tank by an approved tank level-indicating device or method. A measuring stick shall not be used to measure the contents of the tank through the fill connection line, except where there is a direct fill connection.
2305.1.3 Tank connections.
Delivery of liquid motor fuel shall be made by means of approved liquid- and vapor-tight connections between the delivery hose and tank fill pipe. Where tanks are equipped with any type of vapor recovery system, all connections required for the safe and proper functioning of the particular vapor recovery process shall be made. Such connections shall be made liquid- and vapor-tight and remain connected throughout the delivery process. Vapors shall not be discharged at grade level during delivery.
2305.2 Equipment maintenance.
Liquid motor storage and dispensing systems shall be maintained in good working order at all times in accordance with FC 2305.2.1 through 2305.2.3.
2305.2.1 Dispensing devices.
Where maintenance to dispensing devices becomes necessary and such maintenance could allow the accidental release or ignition of liquid, the following precautions shall be taken:
1. Only persons with a certificate of license and knowledgeable in performing the required maintenance shall perform the work.
2. Electrical power to the dispensing device and pump serving the dispenser shall be shut off at the main electrical disconnect panel before maintenance begins.
3. The emergency dispenser shutoff valve shall be closed before maintenance begins.
4. Vehicular traffic and unauthorized persons shall be prevented from coming within 12 feet (3658 mm) of the dispensing device before and during maintenance.
2305.2.2 Dispenser emergency shutoff valves.
Dispenser emergency shutoff valves required by FC 2306.7.4 shall be checked not less than once per year by manually tripping the hold-open linkage.
2305.2.3 Leak detection system.
The leak detection system required by FC 2306.7.7 shall be inspected monthly for proper operation and tested at least annually in accordance with the manufacturer's specifications to ensure that it is in good working order.
2305.3 Use of alcohol-blended motor fuel in existing liquid motor fuel storage and dispensing systems.
Department approval shall be obtained prior to using a liquid motor fuel storage and dispensing system for alcohol-blended motor fuel when such system has previously been used to store and dispense another type of motor fuel. If approved, such system may be used alternatively for the various approved fuel types.
2305.4 Signage.
Durable signs shall be conspicuously posted at motor fuel-dispensing facilities in accordance with this section.
2305.4.1 Tank overfill warning sign.
A warning sign shall be posted on or immediately adjacent to tank overfill alarm panel that reads: "CAUTION: WHEN ALARM ACTIVATES, TANK IS FILLED TO CAPACITY. DO NOT OVERFILL."
2305.5 Portable fire extinguishers.
Approved portable fire extinguishers complying with the requirements of FC 906 with a minimum rating of 40-B:C shall be provided and located such that an extinguisher is not less than 20 feet (6096 mm) but not more than 75 feet (22 860 mm) from pumps, dispensers or storage tank fill connections.