N.Y.C. Admin. Code § FC 5105: Section FC 5105: Outdoor Storage
Where this section sits in the code
- New York City Administrative Code
- Title 29
- Chapter 2: New York City Fire Code
5105.1 General.
The outdoor storage of Level 2 and 3 aerosol products, including storage in temporary storage trailers, shall be separated from exposures in accordance with FC Table 5105.1.
FC Table 5105.1 Distance to Exposures for Outdoor Storage of Level 2 and 3 Aerosol Products
Exposure
Minimum Distance from Aerosol Storage (feet)
a
Public streets or private roads
20
Buildings
50
Exit discharge to a public street or private road
50
Lot lines
20
Other outdoor hazardous material storage
50
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
a. The minimum separation distance indicated is not required where exterior walls having a 2-hour fire-resistance rating without penetrations separate the storage from the exposure. The walls shall extend not less than 30 inches above and to the sides of Level 2 and 3 aerosol products.