N.Y.C. Admin. Code § FC 6204: Section FC 6204: Storage

Read at publisher ↗
Where this section sits in the code
  1. New York City Administrative Code
  2. Title 29
  3. Chapter 2: New York City Fire Code

6204.1 Indoor storage.

Indoor storage of organic peroxides in amounts exceeding the maximum allowable quantity per control area indicated in FC Table 5003.1.1(1) shall be in accordance with FC 5001, 5003, 5004 and this chapter.

6204.1.1 Detached storage.

Storage of organic peroxides shall be in a detached building when required by FC 5003.8.2.

6204.1.2 Distance from detached storage buildings to exposures.

In addition to the requirements of the Building Code, detached storage buildings shall be located in accordance with FC Table 6204.1.2.

FC Table 6204.1.2 Organic Peroxides – Distance from Detached Storage Buildings or Outdoor Storage Areas to Exposures

Organic Peroxide Class

Maximum Storage Quantity (pounds) at Minimum Separation Distance

Distance to buildings, lot lines, public streets, private roads or means of egress

Distance between individual detached storage buildings or individual outdoor storage areas

50 feet

100 feet

150 feet

20 feet

75 feet

100 feet

I

2,000

20,000

175,000

2,000

20,000

175,000

II

100,000

200,000

No Limit

100,000

a

No Limit

No Limit

III

200,000

No Limit

No Limit

200,000

a

No Limit

No Limit

IV

No Limit

No Limit

No Limit

No Limit

No Limit

No Limit

V

No Limit

No Limit

No Limit

No Limit

No Limit

No Limit

For SI: 1 foot = 304.8 mm, 1 pound = 0.454 kg.

a. When the amount of organic peroxide stored exceeds this amount, the minimum separation shall be 50 feet.

6204.1.3 Liquid-tight floor.

In addition to the requirements of FC 5004.12, floors of storage areas shall be of liquid-tight construction.

6204.1.4 Electrical wiring and equipment.

In addition to the requirements of FC 5003.9.4, electrical wiring and equipment in storage areas for Class I or II organic peroxides shall comply with the requirements of the Electrical Code for electrical Class I, Division 2 locations.

6204.1.5 Smoke detection.

An approved supervised smoke detection system in accordance with the construction codes, including the Building Code, shall be provided in rooms or areas where Class I, II or III organic peroxides are stored. Activation of the smoke detection system shall sound a local alarm.

Exception: A smoke detection system shall not be required in detached storage buildings equipped throughout with a fire extinguishing system.

6204.1.6 Maximum quantities.

Maximum allowable quantities per building in a mixed occupancy building shall not exceed the amounts set forth in FC Table 5003.8.2. Maximum allowable quantities per building in a detached storage building shall not exceed the amounts specified in FC Table 6204.1.2.

6204.1.7 Storage arrangement.

Storage arrangements for organic peroxides shall be in accordance with FC Table 6204.2.4 and shall comply with the following requirements:

1. Containers and packages in storage areas shall be closed.

2. Bulk storage shall not be in piles or bins.

3. A minimum 2-foot (610 mm) clear space shall be maintained between storage and uninsulated metal walls.

4. Fifty-five-gallon (208 L) drums shall not be stored more than one drum high.

6204.1.8 Location in building.

Class I or II organic peroxides shall be stored on the ground floor. Class III organic peroxides shall not be stored in basements or other areas below grade.

6204.1.9 Contamination.

Organic peroxides shall be stored in their original DOTn shipping containers. Organic peroxides shall be stored in a manner to prevent contamination.

6204.1.10 Explosion control.

Indoor storage rooms, areas and buildings containing Class I organic peroxides shall be provided with explosion control in accordance with FC 911 and the construction codes, including the Building Code.

6204.1.11 Emergency power.

Emergency power in accordance with the construction codes, including the Building Code and Electrical Code, shall be provided for storage areas of Class I organic peroxides.

6204.1.12 Smoke and heat venting.

Storage areas for Class I organic peroxides shall be provided with smoke and heat venting in accordance with FC 910 and the construction codes, including the Building Code.

6204.2 Outdoor storage.

Outdoor storage of organic peroxides in amounts exceeding the maximum allowable quantities per control area indicated in FC Table 5003.1.1(3) shall be in accordance with FC 5001, 5003, 5004 and this chapter.

6204.2.1 Distance from storage to exposures.

Outdoor storage areas for organic peroxides shall be located in accordance with FC Table 6204.1.2.

6204.2.2 Electrical wiring and equipment.

In addition to the requirements of FC 5003.9.4, electrical wiring and equipment in outdoor storage areas containing Class I or II organic peroxides shall comply with the requirements of the Electrical Code for electrical Class I, Division 2 locations.

6204.2.3 Maximum quantities.

Maximum allowable quantities of organic peroxides in outdoor storage shall be in accordance with FC Table 6204.1.2.

6204.2.4 Storage arrangement.

Storage arrangements shall be in accordance with FC Table 6204.2.4.

FC Table 6204.2.4 Storage Requirements for Organic Peroxides

Organic Peroxide Class

Pile Configuration

Maximum Quantity Per Building

Maximum width (feet)

Maximum height (feet)

Minimum distance to next pile (feet)

Minimum distance to walls (feet)

I

6

8

4

a

4

b

Note c

II

10

8

4

a

4

b

Note c

III

10

8

4

a

4

b

Note c

IV

16

10

3

a, d

4

b

No Requirement

V

No Requirement

No Requirement

No Requirement

No Requirement

No Requirement

For SI: 1 foot = 304.8 mm.

a. At least one main aisle with a minimum width of 8 feet shall divide the storage area.

b. Distance to noncombustible walls is allowed to be reduced to 2 feet.

c. For detached storage buildings or outdoor storage areas, see FC Table 6204.1.2 for maximum quantities. For indoor storage, see FC Table 5003.8.2 for maximum quantities.

d. The distance shall not be less than one-half the pile height.

6204.2.5 Separation.

In addition to the requirements of 5003.9.8, outdoor storage areas for organic peroxides in amounts exceeding those specified in FC Table 5003.8.2 shall be located a minimum distance of 50 feet (15 240 mm) from other hazardous material storage.