N.Y.C. Admin. Code § FGC 415: Section FGC 415: Piping Support Intervals
Where this section sits in the code
- New York City Administrative Code
- Title 28
- Chapter 9: New York City Fuel Gas Code
415.1 Interval of support.
Piping shall be supported at intervals not exceeding the spacing specified in Table 415.1.
Table 415.1 Support of Piping
Steel Pipe, Nominal Size of Pipe (inches)
Spacing of Supports (feet)
1/2
6
3/4 or 1
8
1 1/4 or larger (horizontal)
12
All vertical piping
Every floor level
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.