N.Y.C. Admin. Code § MC 1202: Section MC 1202: Material
Where this section sits in the code
- New York City Administrative Code
- Title 28
- Chapter 8: New York City Mechanical Code
1202.1 Piping.
Piping material, other than those contained within this section and conforming with the ASTM standards listed within this chapter, shall be of an approved type.
Exception: Embedded piping regulated by Section 1209, and ground-source heat pump loop systems regulated by Section 1210.
1202.2 Used existing materials.
Reused pipe, fittings, valves or other materials shall be clean and free of foreign materials.
1202.3 Material rating.
Materials shall be rated for the operating temperature and pressure of the hydronic system. Materials shall be suitable for the type of fluid in the hydronic system.
1202.4 Piping materials standards.
Hydronic pipe shall conform to the standards listed in Table 1202.4. The exterior of the pipe shall be protected from corrosion and degradation.
Table 1202.4 Hydronic Pipe
Material
Standard (see Chapter 15)
Acrylonitrile butadiene styrene (ABS) plastic pipe
ASTM D 1527; ASTM F 2806
Chlorinated polyvinyl chloride (CPVC) plastic pipe
ASTM D 2846; ASTM F 441; ASTM F 442
Copper, brass or copper-alloy pipe
ASTM B 42; ASTM B 43; ASTM B 302
Copper, brass or copper-alloy tube (Type K, L or M)
ASTM B 75; ASTM B 88; ASTM B 135; ASTM B 251
Cross-linked polyethylene/aluminum/cross-linked polyethylene (PEX-AL-PEX) pressure pipe
ASTM F 1281;CSA B137.10
Cross-linked polyethylene (PEX) tubing
ASTM F 876; ASTM F 877
Ductile iron pipe
AWWA C115/A21.15; AWWA C151/A21.51
Polyethylene/aluminum/polyethylene (PE-AL-PE) pressure pipe
ASTM F 1282; CSA B137.9
Polypropylene (PP) plastic pipe
ASTM F 2389
Polyvinyl chloride (PVC) plastic pipe
ASTM D 1785; ASTM D 2241
Raised temperature polyethylene (PE-RT)
ASTM F 2623; ASTM F 2769
Steel pipe
ASTM A 53 / A 53M; ASTM A 106
Steel tubing
ASTM A 254
1202.5 Pipe fittings.
Hydronic pipe fittings shall conform to the respective pipe standards or to the standards listed in Table 1202.5.
Table 1202.5 Hydronic Pipe Fittings
Material
Standard (see Chapter 15)
Copper, brass, and copper alloys
ASME B16.15; ASME B16.18; ASME B16.22; ASME B16.24; ASME B16.26; ASME B16.51; ASTM F 1974
Ductile iron and gray iron
ANSI/AWWA C110/A21.10; AWWA C153/A21.53; ASTM A 126; ASTM A 395; ASTM A 536; ASTM F 1476; ASTM F 1548
Malleable iron
ASME B16.3
PE-RT fittings
ASTM F 1807; ASTM F 2098; ASTM F 2159; ASTM F 2735; ASTM F 2769
PEX fittings
ASTM F 877; ASTM F 1807; ASTM F 2159
Plastic
ASTM D 2466; ASTM D 2467; ASTM F 438; ASTM F 439; ASTM F 877; ASTM F 2389; ASTM F 2735
Steel
ASME B16.5; ASME B16.9; ASME B16.11; ASME B16.28; ASTM A 53/A 53M; ASTM A 106; ASTM A 234; ASTM A 420; ASTM A 536; ASTM A 395; ASTM F 1476; ASTM F 1548
1202.6 Valves.
Valves shall be constructed of materials that are compatible with the type of piping material and fluids in the system. Valves shall be rated for the temperatures and pressures of the systems in which the valves are installed.
1202.7 Flexible connectors, expansion and vibration compensators.
Flexible connectors, expansion and vibration control devices and fittings, when used, shall protect the components of the hydronic system from damage caused by expansion, contraction, transverse movement, angular deflection and vibration, shall be rated for the temperatures and pressures of the systems in which the devices are installed, and shall be compatible with the fluid and all materials provided.
Collected 2026-09-06T02:48:57Z. Source file · JSON