N.Y.C. Admin. Code § MC 1204: Section MC 1204: Pipe Insulation
Where this section sits in the code
- New York City Administrative Code
- Title 28
- Chapter 8: New York City Mechanical Code
1204.1 Insulation characteristics.
Pipe insulation installed in buildings shall conform to the requirements of the New York City Energy Conservation Code, shall be tested in accordance with ASTM E 84 or UL 723, using the specimen preparation and mounting procedures of ASTM E 2231; and shall have a maximum flame spread index of 25 and a smoke-developed index not exceeding 450. Insulation installed in an air plenum shall comply with Section 602.2.1.
1204.2 Required thickness.
Hydronic piping shall be insulated to the thickness required by the New York City Energy Conservation Code.