N.Y.C. Admin. Code § MC 307: Section MC 307: Condensate Disposal

Read at publisher ↗
Where this section sits in the code
  1. New York City Administrative Code
  2. Title 28
  3. Chapter 8: New York City Mechanical Code

307.1 Fuel-burning appliances.

Liquid combustion by-products of condensing appliances shall be collected and discharged to an approved plumbing fixture or disposal area in accordance with the manufacturer's instructions. Condensate piping shall be of approved corrosion-resistant material in accordance with Section 803 of the New York City Plumbing Code and shall not be smaller than the drain connection on the appliance. Such piping shall maintain a minimum horizontal slope in the direction of discharge of not less than one-eighth unit vertical in 12 units horizontal (1-percent slope). Piping shall be configured to permit clearing of blockages and performance of maintenance without requiring the drain line to be cut.

307.1.1 Condensate disposal.

Condensate from all fuel-burning appliances and associated flues shall be neutralized to a pH of at least 6 and no more than 8 prior to disposal to a sanitary system.

307.2 Evaporators and cooling coils.

Condensate drain systems shall be provided for equipment and appliances containing evaporators or cooling coils. Condensate drain systems shall be designed, constructed and installed in accordance with Sections 307.2.1 through 307.2.6.

Exception: Evaporators and cooling coils that are designed to operate in sensible cooling only and not support condensation shall not be required to meet the requirements of this section.

307.2.1 Condensate disposal.

Condensate from all cooling coils and evaporators shall be conveyed from the drain pan outlet to an approved place of disposal. Such piping shall maintain a minimum horizontal slope in the direction of discharge of not less than one-eighth unit vertical in 12 units horizontal (1-percent slope). Condensate shall not discharge into a street, alley or other areas so as to cause a nuisance.

307.2.2 Drain pipe materials and sizes.

Components of the condensate disposal system shall be cast iron, galvanized steel, copper, cross-linked polyethylene, polyethylene, ABS, CPVC, or PVC pipe or tubing. Polypropylene tubing may be used in lengths that do not exceed 12 inches (304.8 mm) for an individual drain application. Components shall be selected for the pressure and temperature rating of the installation. Joints and connections shall be made in accordance with the applicable provisions of Chapter 7 of the New York City Plumbing Code relative to the material type. Condensate waste and drain line size shall be not less than 3/4-inch (19.1 mm) internal diameter and shall not decrease in size from the drain pan connection to the place of condensate disposal. Where the drain pipes from more than one unit are manifolded together for condensate drainage, the pipe or tubing shall be sized in accordance with Table 307.2.2.

Table 307.2.2 Condensate Drain Sizing

Equipment Capacity

Minimum Condensate Pipe Diameter

Up to 20 tons of refrigeration

3/4 inch

Over 20 tons to 40 tons of refrigeration

1 inch

Over 40 tons to 90 tons of refrigeration

1 1/4 inches

Over 90 tons to 125 tons of refrigeration

1 1/2 inches

Over 125 tons to 250 tons of refrigeration

2 inches

For SI: 1 inch = 25.4 mm, 1 ton = 3.517 kW.

307.2.3 Auxiliary and secondary drain systems.

In addition to the requirements of Section 307.2.1, where damage to any building components could occur as a result of overflow from the equipment primary condensate removal system, one of the following auxiliary protection methods shall be provided for each cooling coil or fuel-fired appliance that produces condensate:

1. An auxiliary drain pan with a separate drain shall be provided under the coils on which condensation will occur. The auxiliary pan drain shall discharge to a conspicuous point of disposal to alert occupants in the event of a stoppage of the primary drain. The pan shall have a depth of not less than 1 1/2 inches (38.1 mm), shall be not less than 3 inches (76.2 mm) larger than the unit, or the coil dimensions in width and length and shall be constructed of corrosion-resistant material. Metallic pans shall have a thickness of not less than 0.0236 inch (0.6010 mm) (No. 24 gage) for galvanized sheet metal pans, 0.0179 inch (0.4546 mm) (No. 26 gage) for stainless steel pans, or 0.0320 inch (0.8128 mm) (No. 20 gage) for aluminum pans. Nonmetallic pans shall have a thickness of not less than 0.0625 inch (1.6 mm).

2. A separate overflow drain line shall be connected to the drain pan provided with the equipment. Such overflow drain shall discharge to a conspicuous point of disposal to alert occupants in the event of a stoppage of the primary drain. The overflow drain line shall connect to the drain pan at a higher level than the primary drain connection.

3. An auxiliary drain pan without a separate drain line shall be provided under the coils on which condensate will occur. Such pan shall be equipped with a listed water-level detection device that will shut off the equipment served prior to overflow of the pan. The auxiliary drain pan shall be constructed in accordance with Item 1 of this section.

4. A listed water-level detection device shall be provided that will shut off the equipment served in the event that the primary drain is blocked. The device shall be installed in the primary drain line, the overflow drain line, or in the equipment-supplied drain pan, located at a point higher than the primary drain line connection and below the overflow rim of such pan.

Exceptions:

1. An auxiliary drain protection method shall not be required for fuel-fired appliances that automatically shut down operation in the event of a stoppage in the condensate drainage system.

2. An auxiliary drain protection method shall not be required where a suitably sized and located floor drain is provided.

307.2.3.1 Water-level monitoring devices.

On down-flow units and all other coils that do not have a secondary drain or provisions to install a secondary or auxiliary drain pan, a water-level monitoring device shall be installed inside the primary drain pan. This device shall shut off the equipment served in the event that the primary drain becomes restricted. Devices installed in the drain line shall not be permitted.

307.2.3.2 Appliance, equipment or insulation in pans.

Where an appliance, equipment or insulation is subject to water damage when auxiliary drain pans fill, that portion of the appliance, equipment or insulation shall be installed above the rim of the pans. Supports located inside of the pans to support the appliance or equipment or insulation shall be water resistant and approved.

307.2.4 Traps.

Condensate drains shall be trapped as required by the equipment or appliance manufacturer.

307.2.5 Drain line maintenance.

Condensate drain lines shall be configured to permit the clearing of blockages and performance of maintenance without requiring the drain line to be cut.

307.2.6 Condensate discharge.

Where multiple evaporators and/or condensate pumps discharge into the same piping system, it shall be piped to prevent the discharge of condensate from one appliance to another.

307.3 Exceptions.

This section applies to permanently installed equipment. Window units and through-the-wall air-conditioning units are exempt from the requirements of this section.