N.Y.C. Admin. Code § MC 702: Section MC 702: Inside Air
Where this section sits in the code
- New York City Administrative Code
- Title 28
- Chapter 8: New York City Mechanical Code
702.1 All air from indoors.
Combustion, ventilation, and dilution air shall be permitted to be obtained entirely from the indoors in buildings that are not of unusually tight construction. In buildings of unusually tight construction, combustion air shall be obtained from the outdoors in accordance with Section 703, 705, 706 or 707.
702.2 Air from the same room or space.
The room or space containing fuel-burning appliances shall be an unconfined space as defined in Section 202.
702.3 Air from adjacent spaces.
Where the volume of the room in which the fuel-burning appliances are located does not comply with Section 702.2, additional inside combustion, ventilation, and dilution air shall be obtained by opening the room to adjacent spaces so that the combined volume of all communicating spaces meets the volumetric requirement of Section 702.2. Openings connecting the spaces shall comply with Sections 702.3.1, 702.3.2 and Figure A-1 of Appendix A.
702.3.1 Number and location of openings.
Two openings shall be provided, one within 1 foot (305 mm) of the ceiling of the room and one within 1 foot (304.8 mm) of the floor.
702.3.2 Size of openings.
The net free area of each opening, calculated in accordance with Section 708, shall be a minimum of 1 square inch per 1,000 Btu/h (2201 mm
2
/kW) of input rating of the fuel-burning appliances drawing combustion, ventilation, and dilution air from the communicating spaces and shall be not less than 100 square inches (64 516 mm
2
).
Collected 2026-09-06T02:48:57Z. Source file · JSON