N.Y.C. Admin. Code § PC 502: Section PC 502: Installation
Where this section sits in the code
- New York City Administrative Code
- Title 28
- Chapter 6: New York City Plumbing Code
502.1 General.
Water heaters shall be installed in accordance with the manufacturer's instructions. Oil-fired water heaters shall conform to the requirements of this code, the
New York City Mechanical Code
, and shall comply with UL 732. Approval for oil-fired water heaters 350,000 Btu/h input (102.5 kW) and above shall be obtained from the New York City Department of Environmental Protection. Electric water heaters shall conform to the requirements of this code and provisions of the
New York City Electrical Code
. Domestic electric water heaters shall comply with UL 174 or UL 1453. Commercial electric water heaters shall comply with UL 1453. Gas-fired water heaters shall conform to the requirements of the
New York City Fuel Gas Code
. All water heaters shall conform to the
New York City Energy Conservation Code
.
502.1.1 Elevation and protection.
Elevation of water heater ignition sources and mechanical damage protection requirements for water heaters shall be in accordance with the
New York City Mechanical Code
and the
New York City Fuel Gas Code
.
502.2 Rooms used as a plenum.
Water heaters using solid, liquid or gas fuel shall not be installed in a room containing air-handling machinery where such room is used as a plenum.
502.3 Water heaters installed in attics.
Water heaters installed in attics shall be electric. Attics containing a water heater shall be provided with an opening and unobstructed passageway large enough to allow removal of the water heater. The passageway shall be not less than 30 inches (762 mm) in height and 22 inches (559 mm) in width and not more than 20 feet (6096 mm) in length when measured along the centerline of the passageway from the opening to the water heater. The passageway shall have continuous solid flooring not less than 24 inches (610 mm) in width. A level service space not less than 30 inches (762 mm) in length and 30 inches (762 mm) in width shall be present at the front or service side of the water heater. Dimensions of the clear access opening shall be not less than 20 inches by 30 inches (508 mm by 762 mm) and shall be large enough to allow removal of the water heater.
502.4 Seismic supports.
Where earthquake loads are applicable in accordance with the
New York City Building Code
, water heater supports shall be designed and installed for the seismic forces in accordance with the
New York City Building Code
.
502.5 Clearances for maintenance and replacement.
Appliances shall be provided with access
for inspection, service, repair and replacement without disabling the function of a fire-resistance-rated assembly or removing permanent construction, other appliances or any other piping or ducts not connected to the appliance being inspected, serviced, repaired or replaced. A level working space not less than 30 inches in length and 30 inches in width (762 mm by 762 mm) shall be provided in front of the control side to service an appliance.