N.Y.C. Admin. Code § PC 607: Section PC 607: Hot Water Supply System
Where this section sits in the code
- New York City Administrative Code
- Title 28
- Chapter 6: New York City Plumbing Code
607.1 Where required.
In residential occupancies, hot water shall be supplied to plumbing fixtures and equipment utilized for bathing, washing, culinary purposes, cleansing, laundry or building maintenance. In nonresidential occupancies, hot water shall be supplied for culinary purposes, cleansing, laundry or building maintenance purposes. In nonresidential occupancies, hot water or tempered water shall be supplied for bathing and washing purposes.
607.1.1 Temperature limiting means.
A thermostat control for a water heater shall not serve as the temperature limiting means for the purposes of complying with the requirements of this code for maximum allowable hot or tempered water delivery temperature at fixtures.
607.1.2 Tempered water temperature control.
Tempered water shall be supplied through a water temperature limiting device that conforms to ASSE 1070 and shall limit the tempered water to a maximum of 110ºF (43ºC). This provision shall not supersede the requirement for protective shower valves in accordance with Section 424.3.
607.2 Hot or tempered water supply to fixtures.
The developed length of hot or tempered water piping, from the source of hot water to the fixtures that require hot or tempered water, shall not exceed 20 feet (6096 mm) or the maximum length in accordance with the
New York City Energy Conservation Code
. Recirculating system piping and heat-traced piping shall be considered to be sources of hot or tempered water.
607.2.1 Circulation systems and heat trace systems for maintaining heated water temperature in distribution systems.
For residential occupancies, the installation of heated water circulation and temperature maintenance systems shall be in accordance with the
New York City Energy Conservation Code
. For commercial occupancies that are three stories or less in height above grade plane, the installation of heated water circulation and heat trace systems shall be in accordance with the
New York City Energy Conservation Code
.
607.2.1.1 Pump controls for hot water storage systems.
The controls on pumps that circulate water between a water heater and a storage tank for heated water shall limit operation of the pump from heating cycle startup to not greater than 5 minutes after the end of the cycle.
607.2.1.2 Demand recirculation controls for distribution systems.
A water distribution system having one or more recirculation pumps that pump water from a heated water supply pipe back to the heated water source through a cold water supply pipe shall be a demand recirculation water system. Pumps shall have controls that comply with both of the following:
1. The control shall start the pump upon receiving a signal from the action of a user of a fixture or appliance, sensing the presence of a user of a fixture, or sensing the flow of hot or tempered water to a fixture fitting or appliance.
2. The control shall limit the temperature of the water entering the cold water piping to 104°F (40°C).
607.2.2 Piping for recirculation systems having master thermostatic valves.
Where a thermostatic mixing valve is used in a system with a hot water recirculating pump, the hot water or tempered water return line shall be routed to the cold water inlet pipe of the water heater and the cold water inlet pipe or the hot water return connection of the thermostatic mixing valve.
607.3 Thermal expansion control.
Where a storage water heater is supplied with cold water that passes through a check valve, pressure reducing valve or backflow preventer, a thermal expansion tank shall be connected to the water heater cold water supply pipe at a point that is downstream of all check valves, pressure reducing valves and backflow preventers. Thermal expansion tanks shall be sized in accordance with the tank manufacturer's instructions and shall be sized such that the pressure in the water distribution system shall not exceed that required by Section 604.8.
607.4 Flow of hot water to fixtures.
Fixture fittings, faucets and diverters shall be installed and adjusted so that the flow of hot water from the fittings corresponds to the left-hand side of the fixture fitting.
Exception:
Shower and tub/shower mixing valves conforming to ASSE 1016/ASME A112.1016/CSA B125.16 or ASME A112.18.1/CSA B125.1, where the flow of hot water corresponds to the markings on the device.
607.5 Insulation of piping.
For other than residential occupancies, as defined in the
New York City Energy Conservation Code
that are three stories or less in height above grade plane, piping to the inlet of a water heater and piping conveying water heated by a water heater shall be insulated in accordance with Section C404 of the
New York City Energy Conservation Code
. For residential occupancies, as defined in the New York City Energy Conservation Code that are three stories or less in height above grade plane, piping to the inlet of a water heater and piping conveying water heated by a water heater shall be insulated in accordance with Section R403 of the
New York City Energy Conservation Code
.