N.Y.C. Admin. Code § PC 906: Section PC 906: Vent Pipe Sizing
Where this section sits in the code
- New York City Administrative Code
- Title 28
- Chapter 6: New York City Plumbing Code
906.1 Size of stack vents and vent stacks.
The minimum required diameter of stack vents and vent stacks shall be determined from the developed length and the total of drainage fixture units connected thereto in accordance with
Table 906.1
, but in no case shall the diameter be less than one-half the diameter of the drain served or less than 1 1/4 inches (32 mm).
Table 906.1 Size and Developed Length of Stack Vents and Vent Stacks
Diameter of Soil or Waste Stack (inches)
Total Fixture Units Being Vented (dfu)
Maximum Developed Length of Vent (feet)
a
Diameter of Vent (inches)
1 1/4
1 1/2
2
2 1/2
3
4
5
6
8
10
12
1 1/4
2
30
—
—
—
—
—
—
—
—
—
1 1/2
8
50
150
1 1/2
10
30
100
2
12
75
200
—
—
—
—
—
—
—
2
20
30
50
150
2 1/2
42
26
30
100
300
3
10
—
42
150
360
1,040
—
—
—
—
—
—
3
21
32
110
270
810
3
53
27
94
230
680
3
102
—
25
86
210
620
—
—
—
—
—
4
43
35
85
250
980
4
140
27
65
200
750
4
320
—
—
23
55
170
640
—
—
—
—
4
540
21
50
150
580
5
190
28
82
320
990
5
490
—
—
—
21
63
250
760
—
—
—
—
5
940
18
53
210
670
5
1,400
16
49
190
590
6
500
—
—
—
—
33
130
400
1,000
—
—
—
6
1,100
26
100
310
780
6
2,000
22
84
260
660
6
2,900
—
—
—
—
20
77
240
600
—
—
8
1,800
31
95
240
940
8
3,400
24
73
190
729
8
5,600
—
—
—
—
—
20
62
160
610
—
8
7,600
18
56
140
560
10
4,000
31
78
310
960
10
7,200
—
—
—
—
—
—
24
60
240
740
—
10
11,000
20
51
200
630
10
15,000
18
46
180
571
12
7,300
—
—
—
—
—
—
—
31
120
380
940
12
13,000
24
94
300
720
12
20,000
20
79
250
610
12
26,000
—
—
—
—
—
—
—
18
72
230
500
15
15,000
40
130
310
15
25,000
31
96
240
15
38,000
—
—
—
—
—
—
—
—
26
81
200
15
50,000
24
74
180
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
a. The developed length shall be measured from the vent connection to the open air.
906.2 Vents other than stack vents or vent stacks.
The diameter of individual vents, branch vents, circuit vents and relief vents shall be at least one-half the required diameter of the drain served. The required size of the drain shall be determined in accordance with
Table 710.1(2)
. Vent pipes shall not be less than 1 1/4 inches (32 mm) in diameter. Vents shall be sized in accordance with
Table 906.1
utilizing the drainage fixture units and the corresponding developed length. Relief vents for soil and waste stacks in buildings having more than 10 branch intervals shall be sized in accordance with Section 908.2.
906.3 Developed length.
The developed length of individual, branch, circuit and relief vents shall be measured from the farthest point of vent connection to the drainage system to the point of connection to the vent stack, stack vent or termination outside of the building.
906.4 Multiple branch vents.
Where multiple branch vents are connected to a common branch vent, the common branch vent shall be sized in accordance with this section based on the size of the common horizontal drainage branch that is or would be required to serve the total drainage fixture unit load being vented.
906.5 Ejector vents.
Ejector vent sizes shall be determined in accordance with Sections 906.5.1 and 906.5.2.
906.5.1 Sewage pumps and sewage ejectors other than pneumatic.
Drainage piping below sewer level shall be vented in the same manner as that of a gravity system. Building sump vent sizes for sumps with sewage pumps or sewage ejectors, other than pneumatic, shall be determined in accordance with
Table 906.5.1
. Where a building sump vent connects to a sanitary vent system, the sanitary branch vent shall be at least 3 inches (76 mm) in diameter.
Table 906.5.1 Size and Length of Sump Vents
Discharge Capacity of Pump (gpm)
Maximum Developed Length of Vent (feet)
a
Diameter of vent (inches)
1 1/4
1 1/2
2
2 1/2
3
4
10
No limit
b
No limit
No limit
No limit
No limit
No limit
20
270
No limit
No limit
No limit
No limit
No limit
40
72
160
No limit
No limit
No limit
No limit
60
31
75
270
No limit
No limit
No limit
80
16
41
150
380
No limit
No limit
100
10
c
25
97
250
No limit
No limit
150
Not permitted
10
c
44
110
370
No limit
200
Not permitted
Not permitted
20
60
210
No limit
250
Not permitted
Not permitted
10
36
132
No limit
300
Not permitted
Not permitted
10
c
22
88
380
400
Not permitted
Not permitted
Not permitted
10
c
44
210
500
Not permitted
Not permitted
Not permitted
Not permitted
24
130
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute = 3.785 L/m.
a.
Developed length
plus an appropriate allowance for entrance losses and friction due to fittings, changes in direction and diameter. Suggested allowances shall be obtained from NBS Monograph 31 or other
approved
sources. An allowance of 50 percent of the
developed length
shall be assumed if a more precise value is not available.
b. Actual values greater than 500 feet.
c. Less than 10 feet.
906.5.2 Pneumatic sewage ejectors.
The air pressure relief pipe from a pneumatic sewage ejector shall be connected to an independent vent stack terminating as required for vent extensions through the roof. The relief pipe shall be sized to relieve air pressure inside the ejector to atmospheric pressure, but shall be not less than 1 1/2 inches (38 mm) in size.