N.Y.C. Admin. Code § PC 919: Section PC 919: Engineered Vent Systems
Where this section sits in the code
- New York City Administrative Code
- Title 28
- Chapter 6: New York City Plumbing Code
919.1 General
Engineered vent systems shall comply with this section and Section
28-113.2.2
of the
Administrative Code
.
919.2 Individual branch fixture and individual fixture header vents.
The maximum developed length of individual fixture vents to vent branches and vent headers shall be determined in accordance with
Table 919.2
for the minimum pipe diameters at the indicated vent airflow rates.
The individual vent airflow rate shall be determined in accordance with the following:
Q
h,b
=
N
n,b
Q
v
(Equation 9-1)
For SI:
Q
h,b
=
N
n,b
Q
v
(0.4719 L/s)
where:
N
n,b
= Number of fixtures per header (or vent branch) ÷ total number of fixtures connected to vent stack.
Q
h,b
=
Vent branch or vent header airflow rate (cfm).
Q
v
= Total vent stack airflow rate (cfm).
Q
v
(gpm) = 27.8
r
s
2/3
(1 -
r
s
)
D
8/3
Q
v
(cfm) = 0.134
Q
v
(gpm)
where:
D
= Drainage stack diameter (inches).
Q
w
= Design discharge load (gpm).
r
s
= Waste water flow area to total area.
=
Q
w
/ 27.8
D
8/3
Individual vent airflow rates are obtained by equally distributing
Q
h,b
into one-half the total number of fixtures on the branch or header for more than two fixtures; for an odd number of total fixtures, decrease by one; for one fixture, apply the full value of
Q
h,b
.
Individual vent developed length shall be increased by 20 percent of the distance from the vent stack to the fixture vent connection on the vent branch or header.
Table 919.2 Minimum Diameter and Maximum Length of Individual Branch Fixture Vents and Individual Fixture Header Vents for Smooth Pipes
Diameter of Vent Pipe (inches)
Individual Vent Airflow Rate (cubic feet per minute)
Maximum developed length of vent (feet)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
1/2
95
25
13
8
5
4
3
2
1
1
1
1
1
1
1
1
1
1
1
1
3/4
100
88
47
30
20
15
10
9
7
6
5
4
3
3
3
2
2
2
2
1
1
—
—
100
94
65
48
37
29
24
20
17
14
12
11
9
8
7
7
6
6
1 1/4
—
—
—
—
—
—
—
100
87
73
62
53
46
40
36
32
29
26
23
21
1 1/2
—
—
—
—
—
—
—
—
—
—
—
100
96
84
75
65
60
54
49
45
2
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
100
For SI: 1 inch = 25.4 mm, 1 cubic foot per minute = 0.4719 L/s, 1 foot = 304.8 mm
919.3 A Licensed Professional Engineer shall certify design.
An engineer shall also inspect and certify the system upon completion of the system.