SDCL § 34-18-22.1: Fire safety standards for specialty resort with less than ten occupants.
Where this section sits in the code
- TITLE 34. PUBLIC HEALTH AND SAFETY
- CHAPTER 34-18. HEALTH REGULATION OF LODGING AND FOOD SERVICE ESTABLISHMENTS AND CAMPGROUNDS
Any specialty resort establishment with less than ten occupants shall meet the following minimum fire safety standards:
(1) Any primary exit that leads to the exterior of the structure shall be capable of unlocking from the interior without the use of a key or special knowledge or effort, free from obstruction, and clearly marked with illuminated exit signs. Any sleeping room with a direct exit to the exterior of the building is exempt from this requirement;
(2) There shall be a smoke detector in each sleeping room. The owner or manager shall test any battery operated smoke detector at least twice a year;
(3) Any sleeping room shall be equipped with an operable egress window. Any sleeping room with a direct exit to the exterior of the building is exempt from this requirement; and
(4) Portable fire extinguishers with a minimum 2-A rating shall be made available on each floor and shall be inspected and tagged annually.