- Article 4. Pumping Facilities [Repealed]
A. The pumping station shall be located to meet the hydraulic needs of the distribution system, preserve the quality of the water pumped, and shall consider the availability of a power or a fuel supply.
B. The station shall be:
1. Elevated to a minimum of one foot above the 100-year flood elevation or protected to that elevation;
2. Accessible at all times unless allowed to be out of service by the department;
3. Graded around the station so as to lead surface drainage away from the station; and
4. Protected to prevent vandalism and entrance by animals or unauthorized persons.