No owner or other person shall cause or permit to be discharged into the atmosphere from any Class I unit any nitrogen oxide emissions in excess of the following:

1. For mass burn waterwall units: 200 parts per million by dry volume, measured at 7.0% oxygen, 24-hour daily block arithmetic average concentration.

2. For mass burn rotary waterwall units: 170 parts per million by dry volume measured at 7.0% oxygen, 24-hour daily block arithmetic average concentration.

3. For refuse-derived fuel units: 250 parts per million by dry volume, measured at 7.0% oxygen, 24-hour daily block arithmetic average concentration.

4. For fluidized bed units: 220 parts per million by dry volume, measured at 7.0% oxygen, 24-hour daily block arithmetic average concentration.

5. For mass burn refractory units: 350 parts per million by dry volume, measured at 7.0% oxygen, 24-hour daily block arithmetic average concentration.

6. For modular excess air units: 190 parts per million by dry volume, measured at 7.0% oxygen, 24-hour daily block arithmetic average concentration.

7. For modular starved air units: 380 parts per million by dry volume, measured at 7.0% oxygen, 24-hour daily block arithmetic average concentration.