10 CFR 434.515: Receptacles.

Read at publisher ↗
Where this section sits in the code
  1. Title 10—Energy
  2. CHAPTER II—DEPARTMENT OF ENERGY
  3. SUBCHAPTER D—ENERGY CONSERVATION
  4. PART 434—ENERGY CODE FOR NEW FEDERAL COMMERCIAL AND MULTI-FAMILY HIGH RISE RESIDENTIAL BUILDINGS
  5. Subpart E—Building Energy Cost Compliance Alternative

515.1 Receptacle loads and profiles are default assumptions. The same assumptions shall be made in calculating Design Energy Consumption as were used in calculating the Energy Cost Budget.

515.2 Receptacle loads include all general service loads that are typical in a building. These loads exclude any process electrical usage and HVAC primary or auxiliary electrical usage. Table 515.2, Receptacle Power Densities, establishes the density, in W/ft 2, to be used for each building type. The receptacle energy profiles shall be the same as the lighting energy profiles in Table 513.2.b. This profile establishes the percentage of the receptacle load that is switched on by hour of the day and by building type.

Table 515.2—Receptacle Power Densities

Building type W/ft2 of conditioned floor area

Assembly 0.25

Office 0.75

Retail 0.25

Warehouse 0.1

School 0.5

Hotel/Motel 0.25

Restaurant 0.1

Health 1.0

Multi-family High Rise Residential

Included in Lights and Equipment portions of Tables 512.2 a and b.