GroundRules
← Search the law
Federal regulations · Through 2026-08-25 · Newer source version available

10 CFR 434.518: Service water heating.

Read at publisher ↗
Where this section sits in the code
  1. Title 10—Energy
  2. CHAPTER II—DEPARTMENT OF ENERGY
  3. SUBCHAPTER D—ENERGY CONSERVATION
  4. PART 434—ENERGY CODE FOR NEW FEDERAL COMMERCIAL AND MULTI-FAMILY HIGH RISE RESIDENTIAL BUILDINGS
  5. Subpart E—Building Energy Cost Compliance Alternative

518.1 The service water loads for Prototype and Reference Buildings are defined in terms of Btu/h per person in Table 518.1.1, Service Hot Water Quantities. The service water heating loads from Table 518.1.1 are prescribed assumptions for multi-family high-rise residential buildings and default assumptions for all other buildings. The same service water heating load assumptions shall be made in calculating Design Energy Consumption as were used in calculating the Energy Cost Budget.

Table 518.1.1—Service Hot water Quantities

Building type Btu/person-hour 1

Assembly 215

Office 175

Retail 135

Warehouse 225

School 215

Hotel/Motel 1110

Restaurant 390

Health 135

Multi-family High Rise Residential 2 1700

1 This value is the number to be multiplied by the percentage multipliers of the Building Profile Schedules in Table 513.2.b. See Table 513.2.a for occupancy levels.

2 Total hot water use per dwelling unit for each hour shall be 3,400 Btu/h times the multi-family high rise residential building SWH system multiplier from Table 513.2.b.

518.2 The service water heating system, including piping losses for the Prototype Building, shall be modeled using the methods of the RS-47 (incorporated by reference, see § 434.701) using a system that meets all requirements of subsection 404. The service water heating equipment for the Prototype or Reference Building shall be either an electric heat pump or natural gas, or if natural gas is not available at the site, #2 fuel oil. Exception: If electric resistance service water heating is preferable to an electric heat pump when analyzed according to the criteria of § 434.404.1.4 or when service water temperatures exceeding 145 °F are required for a particular application, electric resistance water heating may be used.

Collected 2026-08-27T02:24:09Z. Source file · JSON

Browse this collection