30 CFR 56.13011: Air receiver tanks.
Where this section sits in the code
- Title 30—Mineral Resources
- CHAPTER I—MINE SAFETY AND HEALTH ADMINISTRATION, DEPARTMENT OF LABOR
- SUBCHAPTER K—METAL AND NONMETAL MINE SAFETY AND HEALTH
- PART 56—SAFETY AND HEALTH STANDARDS—SURFACE METAL AND NONMETAL MINES
- Subpart L—Compressed Air and Boilers
Air receiver tanks shall be equipped with one or more automatic pressure-relief valves. The total relieving capacity of the relief valves shall prevent pressure from exceeding the maximum allowable working pressure in a receiver tank by not more than 10 percent. Air receiver tanks also shall be equipped with indicating pressure gauges which accurately measure the pressure within the air receiver tanks.
Collected 2026-08-27T02:25:24Z. Source file · JSON