30 CFR 75.601-1: -1 Short circuit protection; ratings and settings of circuit breakers.

Read at publisher ↗
Where this section sits in the code
  1. Title 30—Mineral Resources
  2. CHAPTER I—MINE SAFETY AND HEALTH ADMINISTRATION, DEPARTMENT OF LABOR
  3. SUBCHAPTER O—COAL MINE SAFETY AND HEALTH
  4. PART 75—MANDATORY SAFETY STANDARDS—UNDERGROUND COAL MINES
  5. Subpart G—Trailing Cables

Circuit breakers providing short circuit protection for trailing cables shall be set so as not to exceed the maximum allowable instantaneous settings specified in this section; however, higher settings may be permitted by an authorized representative of the Secretary when he has determined that special applications are justified:

Conductor size AWG or MGM Maximum allowable circuit breaker instantaneous setting (amperes)

14 50

12 75

10 150

8 200

6 300

4 500

3 600

2 800

1 1,000

1/0 1,250

2/0 1,500

3/0 2,000

4/0 2,500

250 2,500

300 2,500

350 2,500

400 2,500

450 2,500

500 2,500

Collected 2026-08-27T02:25:24Z. Source file · JSON