40 CFR 141.551: What strengthened combined filter effluent turbidity limits must my system meet?
Where this section sits in the code
- Title 40—Protection of Environment
- CHAPTER I—ENVIRONMENTAL PROTECTION AGENCY
- SUBCHAPTER D—WATER PROGRAMS
- PART 141—NATIONAL PRIMARY DRINKING WATER REGULATIONS
- Subpart T—Enhanced Filtration and Disinfection—Systems Serving Fewer Than 10,000 People
Your system must meet two strengthened combined filter effluent turbidity limits.
(a) The first combined filter effluent turbidity limit is a “95th percentile” turbidity limit that your system must meet in at least 95 percent of the turbidity measurements taken each month. Measurements must continue to be taken as described in § 141.74(a) and (c). Monthly reporting must be completed according to § 141.570. The following table describes the required limits for specific filtration technologies.
If your system consists of * * * Your 95th percentile turbidity value is * * *
(1) Conventional Filtration or Direct Filtration 0.3 NTU.
(2) All other “Alternative” Filtration A value determined by the State (not to exceed 1 NTU) based on the demonstration described in § 141.552.
(b) The second combined filter effluent turbidity limit is a “maximum” turbidity limit which your system may at no time exceed during the month. Measurements must continue to be taken as described in § 141.74(a) and (c). Monthly reporting must be completed according to § 141.570. The following table describes the required limits for specific filtration technologies.
If your system consists of * * * Your maximum turbidity value is * * *
(1) Conventional Filtration or Direct Filtration 1 NTU.
(2) All other “Alternative Filtration” A value determined by the State (not to exceed 5 NTU) based on the demonstration as described in § 141.552.