GroundRules
← Search the law
Federal regulations · Through 2026-08-25 · Newer source version available

40 CFR Table 2 to Subpart Cb of Part 60: Table 2 to Subpart Cb of Part 60—Nitrogen Oxides Limits for Existing Designated Facilities Included in an Emissions Averaging Plan at a Municipal Waste Combustor Plant b

Read at publisher ↗
Where this section sits in the code
  1. Title 40—Protection of Environment
  2. CHAPTER I—ENVIRONMENTAL PROTECTION AGENCY
  3. SUBCHAPTER C—AIR PROGRAMS
  4. PART 60—STANDARDS OF PERFORMANCE FOR NEW STATIONARY SOURCES
  5. Subpart Cb—Emissions Guidelines and Compliance Times for Large Municipal Waste Combustors That are Constructed on or Before September 20, 1994

Municipal waste combustor technology Before April 28, 2009, nitrogen oxides emission limit (parts per million by volume) b On and after April 28, 2009, nitrogen oxides emission limit (parts per million by volume) a

Mass burn waterwall 185 185

Mass burn rotary waterwall 220 190

Refuse-derived fuel combustor 230 230

Fluidized bed combustor 165 165

a Mass burn refractory municipal waste combustors and other MWC technologies not listed above may not be included in an emissions averaging plan.

b Corrected to 7 percent oxygen, dry basis.