46 CFR 108.411: Smoke detection system.
Where this section sits in the code
- Title 46—Shipping
- CHAPTER I—COAST GUARD, DEPARTMENT OF HOMELAND SECURITY
- SUBCHAPTER I-A—MOBILE OFFSHORE DRILLING UNITS
- PART 108—DESIGN AND EQUIPMENT
- Subpart D—Fire Extinguishing Systems
Each smoke accumulator in a smoke detection system must be located on the overhead of the compartment protected by the system in a location—
(a) Where no portion of the overhead of the compartment is more than 12 meters (40 feet) from an accumulator;
(b) That is no closer to the opening of a ventilator than 3 times the diameter or equivalent size of the opening.
(c) Where damage to the accumulator is unlikely to occur if it is not protected.