46 CFR 108.459: Number and location of outlets.
Where this section sits in the code
- Title 46—Shipping
- CHAPTER I—COAST GUARD, DEPARTMENT OF HOMELAND SECURITY
- SUBCHAPTER I-A—MOBILE OFFSHORE DRILLING UNITS
- PART 108—DESIGN AND EQUIPMENT
- Subpart D—Fire Extinguishing Systems
(a) A foam extinguishing system in a space must have enough outlets to spread a layer of foam of uniform thickness over the deck or bilge areas of the space.
(b) A foam extinguishing system in a space that has a boiler on a flat that is open to or can drain into a lower portion of the space must have enough outlets to spread a layer of foam of uniform thickness over the—
(1) Flat; and
(2) Deck or bilge areas of the space.
(c) A foam extinguishing system for a tank must have enough outlets to spread a layer of foam of uniform thickness over the surface of the liquid in the tank.