46 CFR 111.05-27: -27 Grounded neutral alternating current systems.
Where this section sits in the code
- Title 46—Shipping
- CHAPTER I—COAST GUARD, DEPARTMENT OF HOMELAND SECURITY
- SUBCHAPTER J—ELECTRICAL ENGINEERING
- PART 111—ELECTRIC SYSTEMS—GENERAL REQUIREMENTS
- Subpart 111.05—Equipment Ground, Ground Detection, and Grounded Systems
Grounded neutral and high-impedance grounded neutral alternating current systems must have a suitably sensitive ground detection system which indicates current in the ground connection, is able to withstand the maximum available fault current without damage, and provides continuous indication of circuit status to ground. A provision must be included to compare indications under fault conditions with those under normal conditions.
Collected 2026-08-27T02:26:22Z. Source file · JSON