46 CFR 111.05-31: -31 Grounding conductors for systems.

Read at publisher ↗
Where this section sits in the code
  1. Title 46—Shipping
  2. CHAPTER I—COAST GUARD, DEPARTMENT OF HOMELAND SECURITY
  3. SUBCHAPTER J—ELECTRICAL ENGINEERING
  4. PART 111—ELECTRIC SYSTEMS—GENERAL REQUIREMENTS
  5. Subpart 111.05—Equipment Ground, Ground Detection, and Grounded Systems

(a) A conductor for grounding a direct-current system must be the larger of:

(1) The largest conductor supplying the system; or

(2) No. 8 AWG (8.4mm 2).

(b) A conductor for grounding the neutral of an alternating-current system must meet Table 111.05-31(b).

Table 111.05-31(b)—Neutral Grounding Conductor for Alternating-Current System

Size of the largest generator cable or equivalent for parallel generators—AWG-MCM (mm2) Size of the system grounding conductor—AWG(mm2)

Greater than Less than or equal to

2 (33.6) 8 (8.4)

2 (33.6) 0 (53.5) 6 (13.3)

0 (53.5) 3/0 (85.0) 4 (21.2)

3/0 (85.0) 350 MCM (177) 2 (33.6)

350 MCM (177) 600 MCM (304) 0 (53.5)

600 MCM (304) 1100 MCM (557) 2/0 (67.5)

1100 MCM (557) 3/0 (85.0)