46 CFR 111.105-17: -17 Wiring methods for hazardous locations.
Where this section sits in the code
- Title 46—Shipping
- CHAPTER I—COAST GUARD, DEPARTMENT OF HOMELAND SECURITY
- SUBCHAPTER J—ELECTRICAL ENGINEERING
- PART 111—ELECTRIC SYSTEMS—GENERAL REQUIREMENTS
- Subpart 111.105—Hazardous Locations
(a) Through runs of marine shipboard cable meeting subpart 111.60 of this part are required for all hazardous locations. Armored cable may be used to enhance ground detection capabilities. Additionally, Type MC cable may be used subject to the restrictions in § 111.60-23.
(b) Where conduit is installed, the applicable requirements of NFPA 70, Clause 9 of IEC 61892-7: 2019, or Clause 7 of IEC of 60092-502: 1999 (all incorporated by reference; see § 110.10-1 of this subchapter) must be followed. Alternatively, the conduit and cable seals and sealing methods in Clause 6.8 of API RP 14F or API RP 14FZ (both incorporated by reference; see § 110.10-1 of this subchapter) may be followed. Where required by the standard that is applicable to the listed or certified electrical equipment, seal fittings, termination fittings, or glands must be listed or certified by an independent laboratory for use in hazardous locations.
(c) Each cable entrance into Class II and Class III (Zone 20, 21, and 22) equipment must be made with dust tight cable entrance seals approved for the installation.
Collected 2026-08-27T02:26:22Z. Source file · JSON