46 CFR 111.106-5: -5 Cable and wiring.

Read at publisher ↗
Where this section sits in the code
  1. Title 46—Shipping
  2. CHAPTER I—COAST GUARD, DEPARTMENT OF HOMELAND SECURITY
  3. SUBCHAPTER J—ELECTRICAL ENGINEERING
  4. PART 111—ELECTRIC SYSTEMS—GENERAL REQUIREMENTS
  5. Subpart 111.106—Hazardous Locations on OSVs

(a) Cable and wiring in hazardous locations must meet the cable construction and testing provisions of IEEE 1580; ANSI/UL 1309; MIL-DTL-24640C; MIL-DTL-24643C; or 60092-350:2014 and IEC 60092-353:2016 (incorporated by reference, see § 110.10-1), including the respective flammability tests contained therein, and must be of a copper-stranded type.

(b) Type MC cables, when used, must meet the requirements in § 111.60-23 of this part.

(c) For intrinsically safe systems under the standards cited in § 111.106-3(b)(1) and (b)(2) of this subpart, the wiring methods must meet Section 504.30 of NFPA 70 (incorporated by reference, see § 110.10-1). For intrinsically safe systems under the standards cited in § 111.106-3(b)(3) of this subpart, the installation and wiring must meet Clause 7, except for Clause 7.3.1, of IEC 60092-502:1999 (incorporated by reference, see § 110.10-1).