46 CFR 111.15-25: -25 Overload and reverse current protection.
Where this section sits in the code
- Title 46—Shipping
- CHAPTER I—COAST GUARD, DEPARTMENT OF HOMELAND SECURITY
- SUBCHAPTER J—ELECTRICAL ENGINEERING
- PART 111—ELECTRIC SYSTEMS—GENERAL REQUIREMENTS
- Subpart 111.15—Storage Batteries and Battery Chargers: Construction and Installation
(a) An overload protective device must be in each battery conductor, except conductors of engine cranking batteries and batteries with a nominal potential of 6 volts or less. For large storage battery installations, the overcurrent protective devices must be next to, but outside of, the battery room.
(b) Except when a converter is used, the charging equipment for all batteries with a nominal voltage more than 20 percent of line voltage must protect automatically against reversal of current.
Collected 2026-08-27T02:26:22Z. Source file · JSON