46 CFR 111.60-1: -1 Construction and testing of cable.

Read at publisher ↗
Where this section sits in the code
  1. Title 46—Shipping
  2. CHAPTER I—COAST GUARD, DEPARTMENT OF HOMELAND SECURITY
  3. SUBCHAPTER J—ELECTRICAL ENGINEERING
  4. PART 111—ELECTRIC SYSTEMS—GENERAL REQUIREMENTS
  5. Subpart 111.60—Wiring Materials and Methods

(a) Electric cables constructed of stranded copper conductors, thermoplastic, elastomeric or other insulation, moisture-resistant jackets, and, where applicable, armoring and outer-sheathing must meet all the requirements of IEC 60092-350:2014, 60092-352:2005, 60092-353:2016, 60092-354:2014, 60092-360:2014, IEC/TR 60092-370:2009, 60092-376:2017, IEEE 1580, ANSI/UL 1072, ANSI/UL 1309, or MIL-DTL-24640C or MIL-DTL-24643C (all incorporated by reference; see § 110.10-1 of this subchapter), including the respective flammability tests contained therein.

(b) IEC 60092 series cable must meet the Category A or A F/R flammability requirements of IEC 60332-3-22:2009 or 60332-3-21:2000 (both incorporated by reference; see § 110.10-1 of this subchapter).