46 CFR 111.60-13: -13 Flexible electric cord and cables.

Read at publisher ↗
Where this section sits in the code
  1. Title 46—Shipping
  2. CHAPTER I—COAST GUARD, DEPARTMENT OF HOMELAND SECURITY
  3. SUBCHAPTER J—ELECTRICAL ENGINEERING
  4. PART 111—ELECTRIC SYSTEMS—GENERAL REQUIREMENTS
  5. Subpart 111.60—Wiring Materials and Methods

(a) Construction and testing. Each flexible cord and cable must meet the requirements in Sections 4.4.2. and 4.4.6 of IEEE 45.8-2016, Article 400 of NFPA 70, ANSI/NEMA WC-70, or ANSI/UL 62 (all incorporated by reference; see § 110.10-1 of this subchapter).

(b) Application. No flexible cord may be used except:

(1) As allowed under Sections 400.10 and 400.12 of NFPA 70; and

(2) In accordance with Table 400.4 in NFPA 70.

(c) Allowable current-carrying capacity. No flexible cord may carry more current than allowed under Table 400.5 in NFPA 70, or ANSI/NEMA WC-70.

(d) Conductor size. Each flexible cord must be 18 AWG (0.82 mm2) or larger.

(e) Splices. Each flexible cord and cable must be without splices or taps except for a cord or cable 12 AWG (3.3 mm2) or larger spliced for repairs in accordance with § 111.60-19.

(f) Pull at joints and terminals. Each flexible cord and cable must be connected to a device or fitting by a knot, tape, or special fitting so that tension is not transmitted to joints or terminal screws.